Determination of Heat Load Distribution of Air Conditioning Unit for Official Rooms of Kirloskar Block at ITM University

Authors

  • Anshu Raj  Research Scholar, ME Department, ITM University, Gwalior, Madhya Pradesh, India
  • Neelesh Soni  Assistant Professor, ME Department, ITM University, Gwalior, Madhya Pradesh, India

Keywords:

Room sensible heat, Room latent heat, Total heat load

Abstract

In the present scenario due to the effect of Global warming. The temperature of the earth Increasing day by day which causes the requirement of Air conditioning for Domestic as well as official purposes .In this context, for the designing of air conditioning unit for office room of KIRLOSKAR block, ITM UNIVERSITY, GWALIOR. Complete calculation and analysis of heat load distribution inside an office has done, which include determination of total heat available inside the room due to internal as well as external heat sources. For designing of air conditioning unit of KRILOSKAR block having 30 official rooms (excluding laboratories), the heat load calculation has been done. A Single room of KIRLOSKAR blocks KB SF 315, (18040656) cm3, has been consider for determination of total heat load. After calculating the various sensible and latent heat load of room and outside air passing through room, it has been concluded that the Room sensible heat was 5676 W, Room latent heat was 995 W , Outside air sensible heat was 945 W and Outside air latent heat was 880 W. Total heat load was found 1.89 TR for a single room and Sensible heat factor was 0.85.So total air containing load of whole KIRLOSKAR block having 30 official room has been determined (56.7) TR.

References

  1. Prasad Manohar, Refrigeration and air conditioning, New Age International (P) Limited Publishers, 2015, pp. 113-122.
  2. Arora C.P., Refrigeration and air conditioning, McGraw Hill education India private limited, 2014,  pp. 91-93
  3. Nag P.K., engineering thermodynamics, McGraw Hill Education India private limited, 2013, pp.617-19.
  4. Cherem-Pereira G., Mendes N. (2012). Empirical Modeling Of Room Air Conditioners For Building Energy Analysis, Energy And Buildings, Pp: 19-26
  5. SOGUT M. ZIYA (2012). Exergetic and environmental assessment of room air conditioners in turkish market, energy, PP: 3241
  6. Yang Jeong-Hoon, Kim Taeyeon, Cheong Chang Heon (2013). Supply Airflow Control Algorithm of a Floor Standing Room Air-Conditioner to Achieve Thermal Comfort for Residential Housing in summer, Building and Environment, Pp: 227-238
  7. Meissner Jose W., Abadie Marc O. M. Luis Moura, Mendonça Katia C., Mendes Nathan (2014). Performance Curves of Room Air Conditioners for Building Energy Simulation Tools, Applied Energy, Pp: 243-252
  8. Lucas Franck, Ortega Pascal, David Mathieu, Sinama Frantz, Brangeon Boris and Pic Girard Fabien (2015). A Method to Evaluate Energy Performance of Buildings Cooled By Room Air Conditioners, Energy Procardia, Pp.: 1275 – 1283
  9. Zhou Hao Qiao Lifeng, Jiang Yi, Sun Hejiang, Chen Qingyan (2016). Recognition of Air Conditioner Operation from Indoor Air Temperature and Relative Humidity by a Data Mining Approach, Energy and Buildings, Pp.: 233-241
  10. Shuangquan Shao, Weijia Zhang, Hainan Zhang, Hongbo Xul, Changqing Tian (2016). Performance Chart: A Novel Method for Performance Analysis of Multi-Unit Air Conditioners, Energy Procedia, Pp: 552-558
  11. Han Zongwei, Liu Qiankun, Zhang Yanqing, Zhang Shuwei, Liu Jiangzhen, Li Weiliang (2016). Feasibility Study on Novel Room Air Conditioner with Natural Cooling Capability, Applied Thermal Engineering, Pp.: 1310-1319
  12. Kindaichi Sayaka, Nishina Daisaku, Murakawa Saburo, Ishida Masaki, Ando Motoki (2017). Analysis of Energy Consumption of Room Air Conditioners: An Approach Using Individual Operation Data from Field Measurements, Applied Thermal Engineering, Pp.: 7-14
  13. Matsumoto Shigeru, Omata Yukiko (2017). Consumer Valuations of Energy Efficiency Investments: The Case Of Vietnam's Air Conditioner Market, Journal Of Cleaner Production, Pp.: 4001-4010.
  14. Morito Naomi, Tsuzuki Kazuyo, Mori Ikue, Nishimiya Hajime (2017). Effects of Two Kinds of Air Conditioner Airflow on Human Sleep and Thermoregulation, Energy and Buildings, Pp.: 490-498.

Downloads

Published

2017-12-31

Issue

Section

Research Articles

How to Cite

[1]
Anshu Raj, Neelesh Soni, " Determination of Heat Load Distribution of Air Conditioning Unit for Official Rooms of Kirloskar Block at ITM University , International Journal of Scientific Research in Science, Engineering and Technology(IJSRSET), Print ISSN : 2395-1990, Online ISSN : 2394-4099, Volume 3, Issue 8, pp.397-401, November-December-2017.